est 3 lcd display price
The Main Display interface is the primary user interface in the EST3 Life Safety System. The main display interface focuses on the emergency user by putting information important to the user up front. Hands free, the first highest priority event is shown. The display always gives the last highest priority event. Arriving at the panel and without opening the door the first and last alarm is given. Simple to understand lights and switches help the emergency user execute system commands with confidence.
Booster Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs.
Central Processor Unit Module, Mounts to local rail at a dedicated location. Takes two local rail module spaces. Supports 3-LCD(XL), 3-RS485A/B/R, 3-RS232.
Amplifier Terminal Panel. Provides terminals for connection of two amplifiers 1B3-125 or 1B3-250. Provides amplifier battery backup (40 AH max.). 1 required for each 2 amplifiers. Requires 2 supervisory zones to monitor fail conditions and 1 dry relay con
LED Display Support Module. Mounts to local rail and takes one LRM space. Supports one User Interface Module. Use when there are more Display/Control Modules required than LRMs to support them.
Booster Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs.
Booster Power Supply / Charger with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs. Charges 65 AH batteries.
Booster Power Supply / Charger Local Rail Module ONLY. Upgrades 3-BPS/M to 3-BCC/M. Replaces existing 3-BPSMON. Supports one user interface module. Charges 65 AH batteries.
Booster Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs.
Primary Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 A at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs. Charges up to 65 Amp Hour Batteries.
Ten Position Base Annunciator. Includes Door, CPU card, two annunciator support modules and nine blank filler plates. Space provided for up to eight Control/Display Modules and one 3-LCD Liquid Crystal Display Module.
Six Position Base Annunciator. Includes Door, CPU card, two annunciator support modules and five blank filler plates. Space provided for up to four Control/Display Modules and one 3-LCD Liquid Crystal Display Module.
Zoned Amplifier, 20 Watt, Class A/B. 20 Watt selectable for 25 or 70 Vrms Class A/B Output. Mounts in 1 LRM space. Has built in Class A/B NAC rated at 3.5 Amps. Supports one user interface module.
Zoned Amplifier, 20 Watt, Class B. 20 Watt selectable for 25 or 70 Vrms Class B Output. Mounts in 1 LRM space. Has built in Class B NAC rated at 3.5 Amps. Supports one user interface module.
Zoned Amplifier, 40 Watt, Class A/B. 40 Watt selectable for 25 or 70 Vrms Class A/B Output. Mounts in 1 LRM space. Has built in Class A/B NAC rated at 3.5 Amps. Supports one user interface module.
Zoned Amplifier, 40 Watt, Class B. 40 Watt selectable for 25 or 70 Vrms Class B Output. Mounts in 1 LRM space. Has built in Class B NAC rated at 3.5 Amps. Supports one user interface module.
Booster Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs.
Booster Power Supply with Local Rail Module. 120V 50/60 Hz. Takes one Footprint in wallbox and one local Rail module space. Supports one user interface module. Provides 7 amp at nominal 24V dc. Provides two 3.5 Amp auxiliary power limited outputs.
Signature Driver Card with filter. Used to upgrade 3-SSDC to 3-SDDC. Supports one loop of Signature devices up to 125 detector and 125 module addresses.
EST3 supports a full range of annunciator options for Mass Notification/Emergency Communication (MNEC), Life Safety and other purposes. Annunciator cabinets are constructed from 16 gauge cold rolled steel. The gray textured enamel finish of the annunciators complements any decor. Both surface and semiflush mounting cabinet configurations maximize mounting flexibility and esthetic appeal. Cabinet arrangements allow both LED and LCD annunciation to easily combine in a single enclosure. Slide in labeling for LEDs and switches provides designation flexibility for labeling in local languages. For graphic annunciation EST3 offers LED driver boards perfectly suited to operate in most graphic annunciators. EST3 annunciators are perfect for MNEC applications. They can be used in Central Control Stations (CCS), Autonomous Control Units (ACU), Local Operating Console (LOC) and combination units. In these applications, annunciators are configured to operate as Local Operation Consoles, or even Central Command Stations, from which MNEC is initiated and controlled.
Use EST3 remote annunciators when a compact system status display is needed. Annunciator configurations include: LCD only display, LED only displays or combination LED and LCD display in a single enclosure. The LCD display uses either the 3-LCD or 3-LCDXL1 Liquid crystal display module. The 3-LCD has a 128 x 64 graphical display typically used to display eight lines of 21 characters on its LCD display while the 3-LCDXL1 has a larger 240 x 320 pixel backlit display that supports 24 lines of 40 characters. Both LDC displays provide the room needed to convey emergency information in a useful format. The 3-LCD always displays the last highest priority event even when the user is viewing other message queues. To give the greatest message flexibility EST3 event messages can route to specific annunciators. Routing can be initiated at a specific time/ shift change. Messages need only display in areas having to respond to an event. For LED display, the full line of EST3 Control/Display Modules support event display. Control/Display modules install over any annunciator support module maximizing annunciator design flexibility. A Lamptest feature can program to any spare control switch. If an LCD display is installed in the annunciator, simply operate the Alarm Silence and Trouble Silence switches simultaneously to lamptest all LEDs.
The Life Safety system shall incorporate annunciation of Alarm, Supervisory, Trouble and Monitor operations. Annunciation must be through the use of both LED display strips complete with a means to custom label each LED as to its function. Where applicable control switches must be provided. Switches with LEDs must provide positive feed back to the operator of remote equipment status. An LCD display with basic common control LEDs and switches shall be provided. The Common Control Switches and LEDs provided as minimum will be: Reset switch and LED, Alarm Silence switch and LED, Panel Silence switch and LED, Drill switch and LED. It must be possible to add additional common controls as required though the use of modular display / control units. The LCD interface must provide the ability to display custom event messages of a minimum of 40 characters. The LCD must provide the emergency user, hands free viewing of the first and last highest priority event. The last highest priority event must always display and update automatically.
Established in 2003, JKFire commands an unflinching corporate trust in the field of fire, safety and security systems. JK works under the fundamental principle of providing effective systems that preempts any eventuality and defuses potential dangers.
EST EDWARDS 3-LCD FIRE ALARM LIQUID CRYSTAL DISPLAY FOR EST3. EST EDWARDS 3-LCD FIRE ALARM LIQUID CRYSTAL DISPLAY FOR EST3. UNOPENED SEALED BOX. GA TRDTP G140/1G50